SY400K500D Technical Specifications
Symmetra PX 400kW Scalable to 500kW
Brand: Symmetra
Output
Max Configurable Power (Watts)
500.0kWatts / 500.0kVA
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50 Hz, 60 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Other Output Voltages 415
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
10 minutes @ 125% and 30 seconds @ 150%
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full non linear load
Input frequency
40 – 70 Hz (auto sensing)
Input voltage range for main operations
340 – 460 (400V), 408 – 552 (480)V
Input Total Harmonic Distortion
Less than 5% for full load
Type of Input Protection Required
3-pole breaker