GVMRB160KG65S Technical Specifications
Galaxy VM 160 kVA Additional UPS for 1+1 480-480 V
Output
Max Configurable Power (Watts)
144.0kWatts / 160.0kVA
Neutral Output Current
195A
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60 Hz +/-1 Hz
Output Frequency (not synced)
50/60 Hz +/-1 Hz
Load Crest Factor
Unlimited
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Output Voltage THD
< 2% linear load and <3% non-linear load
Output Voltage Tolerance
+/- 1% static and +/- 3% at 100% load step
Bypass
Built-in Static Bypass
Input
Input frequency
40 – 70 Hz
Input voltage range for main operations
360 – 576 (480)V
Input voltage adjustable range for mains operation
360 – 576 (480)V
Input Total Harmonic Distortion
Less than 3% for full load
Type of Input Protection Required
3-pole breaker
Maximum Short Circuit Withstand (Icw)
65.0kAmps
Input Power Factor at Full Load
1.0
Batteries & Runtime
Battery type
No internal battery – uses external battery system
Nominal Battery Voltage
480V
End of Discharge Maximum Battery Current
440.0A
Expected Battery Life (years)
7 – 10
End of Discharge Battery Voltage
384
Efficiency in Battery Operation
95.5 %
Maximum Available Short Circuit Current
65kAmps
Overload Operation
60 seconds @ 125% and 30 seconds @ 150%
Efficiency
View Efficiency Graph