G5TUPS80 Technical Specifications
MGE Galaxy 5000 80 kVA UPS
Output
Max Configurable Power (Watts)
72.0kWatts / 80.0kVA
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50 Hz – programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Other Output Voltages
208, 220, 380, 415
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Output Voltage THD
< 1% linear load and < 2.5% nonlinear load
Output Voltage Tolerance
+/- 1% static and +/- 2 % at 100% load step
Bypass
Internal Bypass (Automatic and Manual), Optional External Bypass
Input
Input frequency
45 – 65 Hz
Input voltage range for main operations
340 – 460 (400V), 408 – 538V
Input Total Harmonic Distortion
Less than 3% for full load
Type of Input Protection Required
3-pole breaker
Other Input Voltages
380, 400, 415
Maximum Short Circuit Withstand (Icw)
30.0kAmps
Input Power Factor at Full Load
1.0