GVX500K750GS Technical Specifications
Galaxy VX 500kVA Scalable to 750kVA 480V
Output
Max Configurable Power (Watts)
750.0kWatts / 750.0kVA
Output Frequency (sync to mains)
60 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Output Voltage THD
< 2% linear load and <3% non-linear load
Output Voltage Tolerance
+/- 1% symmetrical load and +/- 3% asymmetrical lo
Bypass
Built-in Static Bypass, Optional External Bypass
Input
Input frequency
40 – 70 Hz
Input voltage range for main operations
408 – 600VV
Input Total Harmonic Distortion
Less than 3% for full load
Maximum Short Circuit Withstand (Icw)
100.0kAmps
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
No internal battery – uses external battery system
End of Discharge Battery Voltage
384 Vdc
Efficiency
View Efficiency Graph
Communications & Management
Interface Port(s)
GVX_750G_1Feed
Control panel
Touch Screen LCD User Interface
Audible Alarm
Audible and visible alarms : configurable delays
Emergency Power Off (EPO)
Optional
Available SmartSlot™ Interface Quantity
1
Physical
Maximum Height
77.56inches (1970MM, 197.0CM)
Maximum Width
106.3inches (2700MM, 270.0CM)
Maximum Depth
35.43inches (900MM, 90.0CM)
Net Weight
4695.0lbs. (2129.61KG)
Shipping weight
5714.0lbs. (2591.82KG)
Shipping Height
84.65inches (2150MM, 215.0CM)
Shipping Width
124.8inches (3170MM, 317.0CM)